呼伦贝尔Design and calculation of industrial coolers
:本文围绕工业冷却器的设计与计算展开,阐述了工业冷却器在工业生产中的关键作用,其能有效地降低设备或工艺流程的温度,保障系统稳定运行,详细介绍了设计环节,包括依据不同的工业场景和冷却需求确定冷却器的类型,如风冷式、水冷式等,同时考虑冷却介质的特性、流量等参数,在计算方面,着重讲解了热负荷的计算方法,通过分析被冷却对象的热量产生速率、环境温度等因素,精准计算出所需的换热量,还涉及冷却器传热面积、传热系数等关键参数的计算,以确保冷却器能达到预期的冷却效果。
呼伦贝尔1、Design basis
呼伦贝尔Design Standard for Steel Structures GB50017-2017Steel Structure Design Manual, China Construction Industry Press, January 2004
呼伦贝尔
呼伦贝尔Code for Construction and Acceptance of Steel Structures (GB50205-2020)
British Code for Design of Steel Structures (BS5950)
呼伦贝尔
呼伦贝尔2、Design load
呼伦贝尔Load includes structural self weight, wind turbine constant load, live load, snow load, wind load, etc. The structural calculation adopts the ultimate stress method, therefore, the load value is larger than usual. The surface load is calculated based on the distribution coefficient and applied to the platform according to the line load. The wind load is calculated based on the wind vibration coefficient, body shape coefficient, and basic wind pressure to calculate the wind pressure values on four surfaces, which are then converted into line loads and applied to the columns. Auxiliary components such as stair handrails are applied to the stairs according to uniformly distributed loads.
呼伦贝尔
呼伦贝尔1. Constant load
呼伦贝尔
The self weight of the steel structure is automatically calculated by the program, and the node weight is considered based on the self weight of the structure multiplied by 1.3. The weight and fluid load of the radiator are applied by external forces.
Platform constant load: 0.50kN/m2
呼伦贝尔
2. Live load
呼伦贝尔
呼伦贝尔Live load of the platform for loading: 2.5kN/m2
呼伦贝尔
呼伦贝尔3. Snow load
呼伦贝尔
呼伦贝尔According to relevant design data, the snow pressure can be basically calculated as 0.4N/m2.
4. Wind load
Calculate according to the maximum value.
呼伦贝尔
呼伦贝尔Basic wind pressure: 0.35kN/m2, height variation coefficient of 1.8, wind vibration coefficient: 1.5, ground roughness category: Class A
呼伦贝尔
呼伦贝尔Class.
Is the standard value of wind load, is the wind vibration coefficient at height Z, is the shape coefficient of wind load, and is the coefficient of wind pressure height variation.
When the standard value of wind load is less than 0.75kpa, calculate based on 0.75 kPa and multiply by 1.4 times the safety factor. Namely
呼伦贝尔5. Temperature load
呼伦贝尔
The temperature difference is relatively small. The structural form is single, and the linear expansion of steel has a relatively small impact on the overall performance of the structure, which can be ignored.
呼伦贝尔
6 Earthquake loads
呼伦贝尔
According to the seismic analysis design method: small earthquakes do not damage, medium earthquakes are repairable, and large earthquakes do not collapse. Small earthquake analysis can be divided into: bottom shear force method, response spectrum analysis, and elastic time history analysis. Medium earthquake analysis is calculated by multiplying small earthquake analysis by amplification factor.
Seismic fortification intensity: 8 degrees
呼伦贝尔
呼伦贝尔Design basic seismic acceleration peak value: 0.3g
呼伦贝尔Construction site category: II site
呼伦贝尔
Design grouping: Second group
Damping ratio: 0.05
呼伦贝尔This structure adopts MIADS software for overall modeling and analysis. During modeling, beam elements are mainly used for each structure. In order to facilitate loading, plate elements are established at the structural platform. Consolidation is used as the boundary condition at the bottom of each column, and constraints are applied at the connection between the column and the original structure according to the actual situation. The structure includes upright column, cross brace, slant support and upper and lower platform steel structure.
呼伦贝尔
Load sub factors and load combinations:
呼伦贝尔
Number | 呼伦贝尔load | 呼伦贝尔Partial coefficient remarks 呼伦贝尔 | Partial coefficient remarks 呼伦贝尔 |
呼伦贝尔1 呼伦贝尔 | 呼伦贝尔dead load 呼伦贝尔 | 1.3 | |
呼伦贝尔2 呼伦贝尔 | Dead load, when it has a restraining effect on uplift and overturning 呼伦贝尔 | 呼伦贝尔1.0 | |
呼伦贝尔3 呼伦贝尔 | 呼伦贝尔Dead load, when acting together with wind load and live load | 呼伦贝尔1.2 | |
4 | 呼伦贝尔Live load 呼伦贝尔 | 呼伦贝尔1.6 | |
5 呼伦贝尔 | 呼伦贝尔Live load, when combined with wind load 呼伦贝尔 | 1.2 | |
6 | 呼伦贝尔Wind load 呼伦贝尔 | 1.4 | |
7 呼伦贝尔 | When combined with wind load and live load 呼伦贝尔 | 呼伦贝尔1.2 |
呼伦贝尔3、 Radiator calculation
呼伦贝尔
呼伦贝尔1. Material parameters
Aluminum alloy adopts 6005-T1, with tensile strength and yield strength equivalent to 6063-T5, tensile strength ≥ 150Mpa, yield stress ≥ 110 Mpa. According to the performance table of aluminum alloy, it is found that 6063-T5 has a tensile strength of 185Mpa, yield stress of 145 Mpa, and fatigue strength of 90MPa.
呼伦贝尔2. Working condition analysis
呼伦贝尔
呼伦贝尔The calculation of radiators can be divided into 1. lifting ondition,
呼伦贝尔
呼伦贝尔3. operating condition (operating condition is divided into
呼伦贝尔
呼伦贝尔4.support and lifting point participate in force simultaneously.
5.support bears gravity, while lifting point bears horizontal force.
呼伦贝尔
呼伦贝尔6.support does not bear any force, that is, when the overall structure is subjected to uneven settlement, there is a suspension at the bottom)
呼伦贝尔
To ensure its stability, it is recommended that the foundation treatment should be pre compressed and settlement assessment should be carried out during the overall installation.
呼伦贝尔2.1 Hoisting conditions
呼伦贝尔
呼伦贝尔At this point, the radiator is only considered for its own weight due to the lack of fluid injection, and is lifted and installed through a side lifting point. Because no other accessories were installed during modeling, in order to estimate the weight more accurately, its self weight coefficient was defined as 1.3.
呼伦贝尔
呼伦贝尔The radiator structure consists of 1, frame 2, support beam 3, heat exchange tube 4, tube plate, and other ancillary structures. As the heat exchange tube and support beam are fixed together through a corrugated plate, it can be considered that the heat exchange tube participates in the structural stress, which leads to strain and stress generation.
The overall structural model is
呼伦贝尔
Radiator structural model
The overall deformation of the radiator during the lifting process
呼伦贝尔
呼伦贝尔Stress cloud diagram of radiator during lifting process
From its displacement cloud map, it can be seen that its overall deformation is 1.2mm, and the maximum stress is 15MPa
呼伦贝尔
呼伦贝尔
Stress cloud map of heat sink
呼伦贝尔
呼伦贝尔
呼伦贝尔Displacement cloud map of heat sink
呼伦贝尔
From its displacement cloud map, it can be seen that its overall deformation is 1mm and the maximum stress is 2MPa. Through calculation, it can be seen that horizontal lifting has little effect on the heat dissipation fins, and its deformation and stress are far less than the standard requirements.
呼伦贝尔
The vertical lifting situation is as follows:
呼伦贝尔
呼伦贝尔Vertical lifting stress cloud map
呼伦贝尔



还没有评论,来说两句吧...